Summary

  • There is no single best protocol. Each was designed for a particular level of the building. A good architecture connects them instead of replacing them.
  • KNX and DALI control the room, BACnet controls the building services, Modbus and M-Bus read meters, and MQTT and LoRaWAN carry sensor data to platforms.
  • Occupancy data is an input signal for ventilation, lighting, cleaning and space utilisation. A head count gives more than a simple "motion / no motion" detector.
  • Core functions stay local. The building must work without the internet. The cloud optimises, but it does not keep the lights on.
  • Security is designed in from the start: a separate network for building systems, encrypted connections and device updates.

1. The three levels of building automation

LevelWhat is thereTypical protocols
FieldSensors, push buttons, actuators, luminaires, metersKNX, DALI, Modbus RTU, M-Bus, LoRaWAN, EnOcean
AutomationRoom and plant controllers, gatewaysKNX, BACnet, Modbus TCP
ManagementBuilding management system (BMS), analytics platforms, dashboardsBACnet/IP, MQTT, REST API, OPC UA

The classic building protocols grew up on the two lower levels and are optimised for reliable local control. IoT protocols come from the top level and are optimised for moving data over IP networks. A smart building needs both.

2. The protocols in brief

KNX

An open standard for home and building automation (EN 50090, ISO/IEC 14543-3). Devices sit on a shared bus and communicate directly with each other through group addresses, without a central controller. If one device fails, the others keep working. The transmission media are twisted pair (TP), IP and radio (RF). It is configured with one common tool (ETS) for devices from all manufacturers. KNX Secure adds encryption and authentication, and KNX IoT gives external applications access to the data over IP.

Strengths: reliability, vendor independence, long installation life. Limitations: low bus speed, needs a certified integrator, not designed for large volumes of data.

BACnet

A building automation standard (ASHRAE 135, ISO 16484-5), widely used for heating, ventilation and air conditioning and as the common language of BMS systems. Data is represented as objects with properties, such as an analogue input or a schedule. It runs over IP (BACnet/IP) and over RS-485 (MS/TP) for older installations. BACnet/SC adds a secure connection over TLS.

Strengths: a rich data model, with schedules, alarms and trends in the standard itself. Limitations: more complex, and classic BACnet/IP relies on broadcast and has no built-in security.

Modbus

The simplest and most widespread industrial protocol. A master device reads and writes registers in the slaves, over RS-485 (RTU) or Ethernet (TCP). It is found in electricity meters, heat pumps, chillers and inverters.

Strengths: simple, cheap, supported everywhere. Limitations: no description of the data (you need the manufacturer's register map), no security, polling only.

DALI and DALI-2

A lighting control standard (IEC 62386). Each luminaire has an address, can be dimmed individually and can report its status. DALI-2 adds standardised input devices such as presence and light sensors. DALI lines are usually connected to KNX or BACnet through a gateway.

M-Bus and wireless M-Bus

A standard for remote reading of water, heat and electricity meters (EN 13757). It is used when the goal is allocating consumption costs, not real-time control.

MQTT

A lightweight messaging protocol based on publish and subscribe (an OASIS standard, ISO/IEC 20922). Devices publish messages on topics to a broker, and each application subscribes to the topics it is interested in. Sender and receiver do not know each other, which makes adding new consumers of the data easy.

  • Delivery levels (QoS): 0 (at most once), 1 (at least once), 2 (exactly once).
  • Retained messages: a new subscriber immediately receives the last value.
  • Last will: the broker announces when a device drops off the network.
  • Security: TLS and client authentication.

Strengths: small overhead, the connection is opened by the device (convenient behind a firewall), easy to scale. Limitations: the standard does not define message content, so topics and format have to be agreed. The broker is a critical point.

LoRaWAN

A wireless network with long range and very low power consumption. Sensors send small packets to a gateway, which forwards them to a network server. One gateway can cover a whole building, and sensors run for years on a battery. Messages are encrypted with AES-128.

Strengths: no cables, low cost per point, suitable for existing buildings. Limitations: small packets and infrequent transmission (in Europe there is a duty-cycle limit on airtime), so it is not suitable for real-time control.

REST API and webhooks

REST is how applications exchange data over HTTPS: one side asks, the other answers. A webhook is the opposite direction: the system sends a message by itself when an event occurs. They are used to connect platforms, for example an occupancy platform and a booking system.

3. Comparison

ProtocolMain useModelMediumReal timeBuilt-in security
KNXLighting, blinds, room climateDecentralised, event-basedTP bus, IP, RFYesKNX Secure
BACnetHVAC plant, BMSObjects, client and serverIP, RS-485YesBACnet/SC
ModbusMeters and unitsRegister pollingRS-485, EthernetYesNone
DALI-2LightingAddressable devicesTwo-wire lineYesNone
M-BusConsumption meteringPollingTwo-wire line, radioNoWireless variant
MQTTMoving data to platformsPublish and subscribeIPNear real timeTLS
LoRaWANBattery sensorsStar via gatewaySub-1 GHz radioNoAES-128
RESTConnecting applicationsRequest and responseIPNoTLS

4. KNX or MQTT?

The question comes up often, but the two protocols are not alternatives. They solve different problems.

If the task isThe right fit isWhy
A push button switches a lamp, a sensor controls blindsKNXWorks locally and without a server, with guaranteed response
Data from hundreds of sensors reaches an analytics platformMQTTLightweight, scalable, each application subscribes to what it needs
A new building with an automation designKNX, with MQTT for data upstreamControl is in the bus, analysis is in the platform
An existing building without a busLoRaWAN and MQTTNo cabling, sensors are added step by step
A head count controls ventilationBothThe count arrives via MQTT or API, the command is executed via KNX or BACnet

The link between the two worlds is the gateway: a device or piece of software that translates KNX group addresses or BACnet objects into MQTT topics and back.

5. Occupancy data in the building

A simple presence detector only says whether there is movement in a room. A counter says how many people there are. The difference matters for the systems whose load depends on the number of people.

ApplicationWhat is neededAcceptable delayWhere the decision is made
Lighting in a roomWhether people are presentUnder a secondLocally (KNX, DALI)
Ventilation by head countNumber of people in the zoneMinutesLocally or via the platform
Heating and cooling by zoneOccupancy by hour, forecastTens of minutesBMS with data from the platform
Cleaning by usageNumber of visits per dayHoursPlatform
Office space utilisationOccupancy by day and weekDaysPlatform
Capacity limitsCurrent number of peopleSecondsPlatform with an alert

The rule is: the shorter the acceptable delay, the closer to the device the decision has to be.

6. Three architecture patterns

Pattern A: local loop

The sensor is connected directly to the building bus and controls lighting or ventilation without an external system. The most reliable and fastest, but the data stays in the building and is not analysed. Suitable for core functions.

Pattern B: gateway to a platform

Sensors and building systems send data through a gateway to a platform over MQTT or HTTPS. The platform stores, compares and displays, but does not control. Suitable for monitoring, reporting and existing buildings.

Pattern C: the platform sends commands back

The platform calculates setpoints, for example ventilation volume by head count, and passes them to the BMS through an API or gateway. It gives the greatest optimisation, but depends on the connection. So if the connection is lost, the building must fall back to safe local settings.

In practice a combination is used: pattern A for lighting and safety, pattern B for all data, and pattern C for selected functions where the benefit justifies the dependency.

7. How to organise data in MQTT

The standard does not define topics and content, so agree them before the first device. An example structure:

building/floor/zone/device-type/identifier/reading

office-sofia/floor-3/meeting-a/counter/c-0142/occupancy

An example message:

{
  "ts": "2026-06-05T09:15:00Z",
  "occupancy": 7,
  "in": 12,
  "out": 5
}

The example is illustrative and is not the specification of a particular product. Recommendations:

  • Timestamps in UTC and in ISO 8601 format.
  • One reading per topic, or one object with clearly described fields, but not both at once.
  • A retained message for state, so that every new subscriber receives it.
  • A separate topic for device status, and a "last will" to detect sensors that drop out.
  • QoS 1 for readings that must not be lost. QoS 0 is enough for frequent values.
  • Permissions per topic: a device may publish only to its own topic.

8. Security and regulation

  • Separate the building systems network from the office network, with a controlled crossing between them.
  • Encrypt everything over IP: TLS for MQTT and REST, BACnet/SC, KNX Secure in new installations.
  • Change factory passwords and give each device its own credentials.
  • Connections go from the building outwards. Do not open ports to the internet for access to building controllers.
  • Plan updates. A device that cannot be updated is a risk for its whole life.
  • Keep an inventory of devices, their versions and who is responsible for them.

Three European acts affect IoT in buildings. The Data Act, applicable since September 2025, gives the user a right of access to data from connected devices. The Cyber Resilience Act (CRA) introduces security requirements for products with digital elements, with the main obligations applying from December 2027. NIS2 sets risk management requirements for organisations within its scope. For occupancy sensors, also check the data protection requirements in the article Visitor counting and GDPR.

9. Recommendations for roll-out

  1. Start from the goal. Define which decisions will be made from the data, and with what delay. The protocol follows from that.
  2. Describe what is there. Which systems the building has, which protocol they use and who maintains them.
  3. Keep core functions local. Lighting and safety must not depend on the internet.
  4. Choose open standards and require access to the data through an API or MQTT from every supplier.
  5. Agree the data model before installation: zone names, topics, units, time.
  6. Start with one floor or one zone. Check sensor accuracy and the benefit before you expand.
  7. Plan the behaviour on failure of a sensor, gateway and connection, and test it.
  8. Measure the result against a period before the change, under similar external conditions.

10. Where Count2Know fits

The Count2Know platform sits at the management level. It receives data from visitor counters and building sensors, stores it and shows it in one dashboard, and the data is available to other systems through an API.

  • Visitor counters send their data to the platform over the network.
  • Wireless LoRaWAN sensors for climate, air quality, consumption and status connect through a gateway. See the case study Building Monitoring with LoRaWAN Sensors.
  • Meters supply consumption, which is also used to allocate costs between tenants.
  • Output to other systems: REST API and event notifications.

The list of supported systems is on the Integrations page.

Glossary

BMSBuilding management system
HVACHeating, ventilation and air conditioning
GatewayA device or piece of software that translates between two protocols
BrokerThe MQTT server that receives messages and distributes them to subscribers
QoSThe level of delivery guarantee for a message in MQTT
Group addressA KNX address that links the senders and receivers of one function
TLSA protocol for encrypted connections over IP

This paper is for general information. The choice of protocols and architecture for a specific building is made by a designer and a system integrator according to the project and the applicable standards.